Line-Pressurized or Suction

PS&C technicians specialize in testing your pressure or suction lines, utilizing the Estabrooks EZY CHEK PRODUCT LINE TESTER.

In addition to these generalized requirements, testing must be conducted in accordance with the manufacturer’s requirements.

EZY-Chek Manual Line Leak Detector (for Rigid Pipelines) — Certification: Leak rate of 0.1 gph with PD = 98.0% and PFA = 1%.
Leak Threshold: 0.05 pgh. A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
- Maximum pipeline capacity of 426 gallons.

EZY-Chek Manual Line Leak Detector (for Flexible Pipelines) — Certification: Leak rate of 0.1 gph with PD = 99.8% and PFA = 0.2%.
Leak Threshold: 0.05 pgh. A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
- Maximum pipeline capacity of 101 gallons (example: 275 feet of 3 inch line).

UST-Comp allows you the customer to have detailed description of the type of piping, piping configuration, and the condition.

Line testing can be conducted in conjunction with a tank or leak detector test eliminating additional cost for a returned trip charge!!